Magnetizing Inrush Current in Power Transformer

When an electrical power transformer is switch on from primary side, with keeping its secondary circuit open, it acts as a simple induct...

When an electrical power transformer is switch on from primary side, with keeping its secondary circuit open, it acts as a simple inductance. When electrical power transformer runs normally, the flux produced in the core is in quadrature with applied voltage as shown in the figure below. That means, flux wave will reach its maximum value, 1/4 cycle or π/2 angle after, reaching maximum value of voltage wave. Hence as per the waves shown in the figure, at the instant when, the voltage is zero, the corresponding steady state value of flux should be negative maximum. But practically it is not possible to have flux at the instant of switching on the supply of transformer. This is because, there will be no flux linked to the core prior to switch on the supply. The steady state value of flux will only reach after a finite time, depending upon how fast the circuit can take energy. This is because the rate of energy transfer to a circuit cannot be infinity. So the flux in the core also will start from its zero value at the time of switching on the transformer.




If the transformer is switched on at the instant of voltage zero, the flux wave is initiated from the same origin as voltage waveform, the value of flux at the end of first half cycle of the voltage waveform will be,



inrush current
Where φm is the maximum value of steady state flux. The transformer core are generally saturated just above the maximum steady state value of flux. But in our example, during switching on the transformer the maximum value of flux will jump to double of its steady state maximum value. As, after steady state maximum value of flux, the core becomes saturated, the current required to produced rest of flux will be very high. So transformer primary will draw a very high peaky current from the source which is called magnetizing inrush current in transformer or simply inrush current in transformer.
inrush current


Magnetizing inrush current in transformer is the current which is drown by a transformer at the time of energizing the transformer. This current is transient in nature and exists for few milliseconds. The inrush current may be up to 10 times higher than normal rated current of transformer.


Although the magnitude of inrush current is so high but it generally does not create any permanent fault in transformer as it exists for very small time. But still inrush current in power transformer is a problem, because it interferes with the operation of circuits as they have been designed to function. Some effects of high inrush include nuisance fuse or breaker interruptions, as well as arcing and failure of primary circuit components, such as switches. High magnetizing inrush current in transformer also necessitate over-sizing of fuses or breakers. Another side effect of high inrush is the injection of noise and distortion back into the mains.

COMMENTS

Name

BASIC ELECTRICAL,12,BATTERIES,4,CIRCUIT THEORIES,9,CONTROL SYSTEMS,3,DC MOTOR,1,DIGITAL ELECTRONICS,1,DISTRIBUTED GENERATION,2,DISTRIBUTION,6,ELECTRICAL DRIVES,1,ELECTRICAL LAWS,8,ELECTRONICS DEVICES,2,General,7,GENERATION,3,GENERATOR,1,HIGH VOLTAGE,4,ILLUMINATION,1,INDUCTION MOTOR,7,MATERIALS,1,MEASUREMENT,1,MOTOR,1,POWER ELECTRONICS,2,PROJECTS ON INDUCTION MOTOR,1,PROTECTION,1,SMART GRID,3,SWITCHGEAR,4,SYNCHRONOUS MOTOR,1,TRANSFORMER,6,TRANSMISSION,4,
ltr
item
Electrical for Us: Magnetizing Inrush Current in Power Transformer
Magnetizing Inrush Current in Power Transformer
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEhfSVGn_R-RZbee8x0JMmtaNswv6K4alt16gONqzUYWacNS_outWXsSNZ4Zt9FB_ICFTwn5rcunzPF95nq_ETHk3ZqgAap25AfzlGlPPYDGUiaxJ-nr3-IfGB52sIrhLGKPwzCL0M-fzirm/s320/transformer.jpg
https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEhfSVGn_R-RZbee8x0JMmtaNswv6K4alt16gONqzUYWacNS_outWXsSNZ4Zt9FB_ICFTwn5rcunzPF95nq_ETHk3ZqgAap25AfzlGlPPYDGUiaxJ-nr3-IfGB52sIrhLGKPwzCL0M-fzirm/s72-c/transformer.jpg
Electrical for Us
https://www.sanjaysah.com.np/2016/12/magnetizing-inrush-current-in-power.html
https://www.sanjaysah.com.np/
http://www.sanjaysah.com.np/
http://www.sanjaysah.com.np/2016/12/magnetizing-inrush-current-in-power.html
true
3851448774078769448
UTF-8
Loaded All Posts Not found any posts VIEW ALL Readmore Reply Cancel reply Delete By Home PAGES POSTS View All RECOMMENDED FOR YOU LABEL ARCHIVE SEARCH ALL POSTS Not found any post match with your request Back Home Sunday Monday Tuesday Wednesday Thursday Friday Saturday Sun Mon Tue Wed Thu Fri Sat January February March April May June July August September October November December Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec just now 1 minute ago $$1$$ minutes ago 1 hour ago $$1$$ hours ago Yesterday $$1$$ days ago $$1$$ weeks ago more than 5 weeks ago Followers Follow THIS CONTENT IS PREMIUM Please share to unlock Copy All Code Select All Code All codes were copied to your clipboard Can not copy the codes / texts, please press [CTRL]+[C] (or CMD+C with Mac) to copy